# General FINMON Programming

This page covers the essential programming requirements for all Finmon radio installations.

---

#### Required Programming Steps

The following must be programmed for the Finmon radio to work via the dialler correctly:

1. **Account Code**
   - Four digit code as required by control room
   - Must be inserted in all required locations (some panels need it in multiple places)
   - For six digit fields: program the four digits followed by FF (e.g., 1234FF)

2. **Telephone Number**
   - Program '5555555' in both primary and secondary locations
   - Must be exactly seven 5's

3. **Communication Format**
   - Contact ID must be enabled
   - This is the standard format for all installations

4. **Dial Attempts**
   - Minimum of 6 attempts required

5. **Dial Timeout**
   - For kiss-on (if applicable): minimum 60 seconds
   - If no timeout available, ensure attempts cover:
     - 90 seconds for server send
     - Additional 90 seconds for direct send
     - SMS send time (if enabled)
   - **Note:** SMS limit is 20 free messages per unit per month

6. **Dialing Method**
   - Tone dialling must be enabled (usually default)
   - Do not use pulse dialling

7. **Special Requirements**
   - Forced dialling must be enabled (mostly for Caddx panels)

---

#### Important Notes

- Always verify all settings before leaving site
- Test communication after programming
- Document any deviations from standard programming