IDS805 Programming
IDS805 panels with grey serial cable on external serial connector
Basic Programming
Locations 43 to 46
- Enter [Account code]
Location 47
- Enter 6 (Contact ID)
Locations 48 to 54
- Enter 5555555
Location 151
- Default is 4 dial attempts
- Enter 0 to disable the dialer
Important Notes
- Tone and force dialling are enabled by default
- LTE GSM must be powered directly from battery
- Do not power from panel auxiliary output
App Configuration
For mobile app connectivity:
Requirements:
- App version v4.37 or latest vE4.xx
- Serial Port must be set to Orisec/IDS805
- Requires a VALID user code
- ONLY POWER FROM THE SERIAL (no external power)
Troubleshooting
- If no communication, verify power is from battery
- Test with known working user code