Paradox Evo 192 Triggers

Configuration for direct trigger inputs using PGM outputs


Prerequisites

Before starting:

  1. Ensure jumper for PGMs is set to positive on panel motherboard
  2. If not set:
    • Shut down panel
    • Change jumper position
    • Power up again

Important: PGM1 stays negative - only PGM 2, 3, and 4 become positive


PGM2 Configuration (Panic)

Location 0920

  • Enter: 030 255 000 000

Location 0928

  • Enter: 005

Location 0929

  • LEDs 1 and 3 ON

PGM3 Configuration (Burglary)

Location 0930

  • Enter: 024 255 000 000

Location 0938

  • Enter: 005

Location 0939

  • LEDs 1 and 3 ON

PGM4 Configuration (Open and Close)

Location 0940

  • Enter: 064 255 000 000

Location 0948

  • Enter: 000

Location 0949

  • All LEDs OFF

Wiring Notes

  • Connect radio's Z4 (AC fail) to 1st AC connect block on panel
  • Keep PGM wiring away from high voltage lines
  • Test each PGM after configuration