IDS X64 Programming
Complete guide for all X64 variants
Basic Programming (All Versions)
Location 41
- Default setting usually fine
- Set to 5 for Contact ID on Telephone Number 1
Location 46
- Subloc 1 (LED 1): ON for Tone dialling
- Subloc 2 (LED 2): OFF
- Subloc 3 (LED 3): OFF
Location 47
- Set to 6
Location 51
- Enter 5555555 (seven 5's)
Location 61-68 (Account Codes)
- Loc 61: Partition 1 account code (4 digits)
- Loc 62: Partition 2 account code
- Loc 63-68: Partitions 3-8 account codes
Location 71 (72 = P2 -> 78 = P8)
- Serial account code (same as partition account code)
Location 196
- Must be 000000
Location 501-564
- Option 3 must be set to Yes
Enable User Code Bypassing Hold [ * ] → beep → [MASTER CODE] [ * ] [ 1 ] [ 0 ] [ * ] [USER CODE] [ * ] [BITMAP] [ * ] [ # ]
Bitmap(Option 8) Zone Bypass Enable MUST be set to Yes
Open/Close Reporting by User
For X64 Older than 2017
Programming Sequence: Hold [ * ] → beep → [ MASTER CODE ] [ * ] [ 1 ] [ 4 ] [ * ] [ USER CODE ] [ * ] [ BITMAP ] [ * ] [ # ]
Enable User Reporting Codes:
Subloc/LED | Default | Action |
---|---|---|
1 | OFF | Set ON to enable close reporting |
2 | OFF | Set ON to enable stay close reporting |
3 | OFF | Set ON to enable open reporting |
4 | OFF | Set ON to enable siren cancel reporting |
Important: Must be repeated for EACH user requiring open/close reporting!
For X64 New (2017 onwards)
- Enter Installer Mode
- Go to Partition Arm Options (Locations 211-218)
- Enable option 16 (Open/Closing User Reporting), this option is global for all users in the partition.
Arm Without User Code Reporting
For quick-arm and key-switch arming:
Locations 581-588 (Split Reporting Data)
- Subloc 7: Set ON to enable "Armed without user code" reporting
- Location 581 for Partition 1
- Location 582 for Partition 2
- Locations 583-588 for Partitions 3-8
Serial/App Programming
Requirements:
- Panel firmware: V2.80 or above
- GSM firmware: V4.51 or above
- Draw power from Aux 12V, NOT from serial cable
Programming:
- Loc 40: Ensure value 5 (CID) is programmed
- Loc 61: Account code required
- Loc 196: Must be 000000
24V Version Additional:
- Loc 71: Account code required
Troubleshooting
- If you can connect but get Bypassed zones and are unable to do anything: Check Loc 196 = 000000
- After changing Loc 196: Remove panel from app and re-add
- Cannot control panel: Verify user code
- Connection issues: Check power source (must be Aux 12V)
Everything up to and including the IDS Panels is complete.